The IRIS 600 flame ionisation relay is used in conjunction with a flame rod to detect the presence of a flame.

  • Ten-segment bar graph display to indicate flame signal strength with a reenergising flame relay.
  • Plug-in, for ease of maintenance
  • Plug-in with power indication.
  • Voltage selector switch 110/230 VAC.
  • Power Supply    110 volts 50/60 hz or 230 volts 50/60 hz
  • Voltage Tolerance   +10% to -15%
  • Power Consumption      8VA
  • Ambient Temperature  -20 to +70 degrees C
  • Degree of Protection     IP 40
  • Contact Rating   1 amp @ 24vdc
  • 0.5 amp @ 110/230 vac
  • Flame Failure Response Time     Less than 1 second