Honeywell Model 700 Signal Processor

Model 700 Signal Processors are Single – Channel, Fail Safe, Self – Checking Flame Monitoring Systems when used in Conjunction with the S70X/S80X Series Viewing Heads.

They offer Easy Setup, Medium Level Discrimination and High Reliability​.

  • Models Available in AC (700ACSP) or DC (700DCSP) Input Voltage
  • Intuitive Keypad for Easy Setup and Configuration
  • Two – Digit Numeric Display and Four LED Status Indicators
  • Compact DIN Rail Mountable Design Utilizes Only Three Inches of Space
  • Plug – In Terminal Connectors Allow for Easy Installation
  • Low Power Consumption
  • Environmentally Sealed Switches
  • Modbus RS422 Communication for Use with FLAMETOOLS – PC or FLAMETOOLS – HMI/U Supports 32 Loops
  • Primary Input Power for Model 700ACSP is 85 to 265 VAC, 50 or 60 Hz, 0.07 A Max with 24 VDC Backup Power
  • Primary Input Power for Model 700DCSP is 22 to 26 VDC, 250 mA max with 24 VDC Backup Power
  • Ambient Temperature: 32°F to 140°F (0°C to 60°C)
  • Flame Relay: 2 Form C Contacts
  • Self – Checking Relay: 1 Form C Contact
  • Relay Contact Ratings: 5 A at 125 VAC, 277 VAC, & 30 VDC; 1/8 HP 125 & 250 VAC
  • Analog Flame Signal: Isolated 0-20 mA or 4-20 mA Output for Remote Meters
  • Auto Burner Configuration for Burner On/Off
  • Adjustable Flame Relay On/Off Set Point
  • Adjustable FFRT 1, 2, or 3 Seconds
  • 2 – 4 Burners Steam Generator
  • Duct Burners
  • Multiple Burner Heaters
  • Furnaces and Reformers
  • Natural Draft Burners

700ACSP – 85 to 265 VAC

NOT IN STOCK (Available For Back-Order)

700DCSP – 22 to 26 VDC

NOT IN STOCK (Available For Back-Order)